| datasheetdetails | 
| | <<  |  <  |   AX-GS-CD-D80 - Duct Carbon Dioxide Sensor 
 |  |  |  |  | 
| The AX-GS-CD-D80 Carbon Dioxide Duct mounted Transmitter uses NDIR single beam Infra-red technology to monitor CO2 concentration levels and output a corresponding 0-10V output. The unit is intended for use in return air ducts. | 
 | Product Features 
 |  | • Duct mounting • Monitors CO2 over range 0-2,000 ppm
 • Optional 105 and 205mm probe lengths
 
 | • Solid state sensing element • Lifetime calibration interval
 • Gas permeable PTFE filter
 
 | 
 
| Power Supply D8041/2 
 | 18 to 30Vac 50/60Hz or 18 to 42Vdc 
 |  | Consumption D8041/2 
 | 0.65W @nominal voltage of 42Vdc (max 1.65W peak) 
 |  | Power Supply D8041M/2M 
 | 90 to 265Vac 
 |  | Consumption D8041M/2M 
 | 0.7W (max 1.7W peak) 
 |  | Ambient Temp. Range 
 | 0 to +50’C , 0-95% RH non condensing 
 |  | Duct Air Velocity 
 | 0 - 450m/min 
 |  | Housing 
 | Flame retardant ABS 
 |  | Dimensions Housing 
 | 77 x 77 x 40 mm 
 |  | Dimensions Probe 41 
 | 105 x 32 mm 
 |  | DimensionsProbe 42 
 | 205 x 32 mm 
 |  | Analogue Output 
 | 0-10V at 5mA max 
 |  | Sensor Type 
 | Non-dispersive Infra-red 
 |  | Range 
 | 0-2000ppm standard, 
 |  | Calibration Interval 
 | Lifetime 
 |  | Accuracy 
 | +/- 40ppm or 3% whichever is greater 
 |  | Stability 
 | Self Calibrating <2% FS over life of sensor (typical 10yrs) 
 |  | Linearity 
 | <1% FS @22 degC 
 |  | Settling Time 
 | <2 minutes after power up (10 minutes maximum accuracy) 
 |  | Conformity 
 | CE marked, EMC, LVD. 
 |  | Country of Origin 
 | UK and Mexico 
 | 
 
| AX-GS-CD-D80.pdf /  Duct carbon dioxide sensor. |  | 
 | 
 | 
 |