datasheetdetails
|
<< | < | AX-GS-CM-M-SQ - Carbon Monoxide Sensor Output - Square Enc MODBUS RTU
|
|
The AX-GS-CM-M-SQ is an optimal solution for detecting hazardous emissions in parking garages, loading docks, warehouses, and other similar environments. It employs an electrochemical sensor to monitor carbon monoxide (CO) concentration levels ranging from 0 to 300 parts per million (ppm). The device transmits data over the RS-485 network using the Modbus RTU protocol. By continuously monitoring CO levels, the ventilation system can be adjusted accordingly to maintain air quality within safe limits.The sensor module utilizes a plug-in connector, facilitating effortless replacement in the field. |
Product Features
| • Monitors CO levels over a range of 0 to 300ppm • Easy maintenance and 3 year exchange sensor option • Electrochemical sensing element • Sensor is UL recognised component UL2034, UL2075,
| • Isolated RS-485 Output E240671 • Comes with Square Enclosure • 3 Year Warranty
|
Sensor Type
| CO
| Temperature (option)
| 10K3A1 NTC Thermistor
| Power Supply
| 24Vac ±10%, 100mA maximum or 24Vdc ± 10%, 60mA maximum
| Output
| Isolated RS-485 Modbus RTU
| Supported baud rates
| 9600,19200,38400,57600,115200bps. More info in installation manual.
| Output Accuracy
| CO
| Temperature (option)
| ±0.3 °C Typical
| Output Stability
| <5% signal drift per year
| Typical Coverage Area
| 700m² or 15m radius
| Settling Time
| 3 minutes after power up
| Response Time(t90)
| <35 Seconds
| Life Expectancy
| >3 years dependant on environment
| Ambient Range
| 0-50°C, 1590% RH noncondensing
| Housing
| Polypropylene, IP66, White (optional Black - see order codes)
| Dimensions & Weight
| 140grams, 85 (W) x 85 (L) x 50 (D) mm
| Terminals
| Rising clamp for 0.5-1.5mm²
| Country of origin
| UK
|
AX-GS-CM-M-SQ.pdf / Carbon Monoxide Transmitter MODBUS RTU | |
|
|
|