datasheetdetails
|
<< | < | AX-GS-CM-I - Carbon Monoxide Sensor Current Output
|
|
The AX-GS-CM-V-65 Carbon Monoxide Current transmitter provides a linear 4-20mA output signal for CO levels from 0-300ppm or 0-100ppm. Options include relay(s) with set trip points. The sensor module uses a plug-in connector, making for easy in-the-field replacement. |
Product Features
| • Monitors CO levels over a range of 0 to 100/300ppm • Electrochemical sensor element • Relay(s) options with jumper selectable alarm levels (AX-GS-CM-I3xx versions only) • Easy installation with plug-in connections
| • 3 year warranty • 4-20mA 2-wire loop powered (AX-GS-CM-ILPxx only) • Easy maintenance and 3 year sensor exchange option • Sensor is UL recognised component UL2034, UL2075, E240671
|
Sensor Type
| Electrochemical 3-electrode
| Power Supply
|
| AX-GS-CM-ILP
| 24Vdc ±10%, 2 wire loop powered
| AX-GS-CM-I3
| 24Vdc ±10%, 30mA maximum or 24Vac ±10%, 35mA max
| AX-GS-CM-I3R,R2
| 24Vdc ±10%, 50mA maximum or 24Vac ±10%, 65mA max
| Output
| 4-20mA into 500Ohms max load
| Relay options
|
| AX-GS-CM-I3R
| SPCO relay, 230Vac 5A (resistive)
| AX-GS-CM-I32R
| 2 SP relays common connection, 50V 1A (resistive)
| Output Range
| 0-300ppm or 0-100ppm
| Output Accuracy
| ±5ppm or ±5% of reading (whichever is greater) between 0-50°C
| Output Stability
| <5% signal drift per year
| Typical Coverage Area
| 700m² or 15m radius
| Settling Time
| 3 minutes after power up
| Life Expectancy
| >3 years dependant on environment
| Ambient Temp. & Humidity Range
| 0-50°C, 15-90% RH non-condensing
| Housing
| Flame retardant ABS, IP65
| Dimensions & Weight
| 92mm diameter x 52mm, 170gms
| Fixing Holes
| 4mm holes, 92mm between centres
| Terminals
| Rising clamp for 0.5-1.5mm²
| Country of Origin
| United Kingdom
|
AX-GS-CM-I.pdf / Carbon Monoxide Current transmitter | |
|
|
|