The AX-CNDR-A32x analogue room controllers feature a high-contrast blue backlit display with white text, and fit a standard single gang patress. The unit has selection for an internal or external temperature sensors and provides on/off heating and cooling control. The cleardisplay indicates room temperature, fan speed, occupancy and window status. The unit has a keycard/occupancy input with adjustable set back and exit delay and awindow contact input. The unit should be used with an AX-CNDR-RMA-3x remote relay module. The AX-CNDR-RMA-3x are remote relay modules for use with the AX-CNDR-A32x thermostats. The modules have interlocked 3-Speed fan, and On/Off heating/cooling relays. The AX-CNDR-A32B analogue room controllers also provides network connectivity with an isolated BACnet MSTP link, supporting COV. |
Product Features
| • On/off heating/cooling control • 3 speed fan speed control with Auto mode • Interlocked relays allow only one fan output on at a time • Isolated BACnet MSTP / RTU, supports COV (A32B) • Adjustable setpoint range
| • Keycard / occupancy input, adjustable exit delay • Window contact input • Unused Keycard / Window contact inputs available as digital inputs • Two part plug-in connectors for easy installation • Built in terminating resistor (A32B)
|
Product specifications
| AX-CNDR -A3B / -A3 controllers
| Supply From
| AX-CNDR-RMA-3x
| Inputs
| External temperature sensor, 10K3 Keycard and Window inputs for volt free contacts
| Outputs
| Connected to AX-CNDR-RMA-3x
| Network (A3B)
| BACnet MSTP
| Baud rates (A3B)
| 9K2, 19K2, 38K4, 57K6, 76K8 and 115K2
| Terminals
| Rising clamp for 0.5-1.5mm² cable
| Dimensions & weight
| 86 x 86 x 35mm,TBC
| Housing
| Brushed Stainless steel to fit 35mm deep single back box
| Ambient Temperature
| 0 to 50°C
| Country of Origin
| United Kingdom
|
|
| Product specifications
| AX-CNDR-RMA -32 / -31 relay modules
| Supply
| 230Vac +/- 10% 50/60Hz
| Fuse
| 315mA, 230V
| Inputs
| External temperature sensor feed through
| Outputs
| Fan 12A at 250Vac resistive (Inductive typically 5A)
| Outputs
| On/off 6A at 250Vac resistive.
| Terminals
| Rising clamp for 0.5-1.5mm² cable
| Dimensions & weight 156 x 86 x 58mm, TBC
|
| Housing
| IP flame retardant ABS
| Ambient Temperature
| 0 to 50°C
| Country of Origin
| United Kingdom
|
| AX-CNDR-A32x.pdf / Dig Room Controller (BACnet) with Relay Module |  |
|
|
|